Connecting the Cable (cont.)E-10Wiring Diagram of Power CableWhen using ELBs for 3 phase and 1 phaseWhen using an ELB for 3 phase 4 wiresMCCBELB ELBMC
E-11ENGLISHWiring Diagram of Connection CordConnection Cord SpecificationsIndoor Unit 1Outdoor UnitType A Outdoor unitIndoor Unit 2 Indoor Unit 3220V/
Piping and refnet joint selectionE-12Outdoor unitOutdoor unitOutdoor unit112 2 2 3 3 3 4 4 55566 7 7 7 8 8 8614 11223344 5 5668877Outdoor unitOut
E-13ENGLISHLimitation when piping is installed by using only Refnet joint(during 6 rooms installation)Outdoor unitab123456cdehgijkfH1H2Max. allowablel
E-14Piping and refnet joint selection (cont.)Requirement when piping is installed using simultaneously bothrefnet joint and contributor kit (during 6
E-15ENGLISHInstall the oil trap◆ Install the oil trap in case that the outdoor unit is situated higher than theindoor unit.◆ Install the oil trap only
Connecting the Refrigerant PipeRefrigerant PipingThe refrigerant pipe can be connected from the bottom or front of the outdoor unit. You have to use s
Performing Leak Test & Vacuum DryingBefore completing the installation(insulation of the hose and piping),you must check that there are no gas lea
Performing Leak Test & Vacuum Drying (cont.)◆ When you use the service port, always use a charging hose, too.◆ Check the leakage of refrigerant g
InsulationOnce you have checked that there are no leaks in the system, you caninsulate the piping and hose.To avoid condensation problems, place an in
Parts List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33OOOOPPPPTTTTIIIIOOOONNNNAAAALLLLAAAACCCCCCCCEE
Adding RefrigerantThe outdoor unit is loaded with sufficient refrigerant for the standard piping. Thus, refrigerant must be added if the piping is len
How to Calculate the Quantity of Adding RefrigerantOuter diameter of liquid refrigerant pipeQuantity of addingrefrigerant per metre6.35mm50g/m9.52mm80
Adding Refrigerant (Cont.)‹A B C12 344000W4000W 2000W 2000W 2000W10000W6000W❋ Quantity of adding refrigerant= (Length of ø9.52 liquid pipe x 80g/m) +
◆Quantity of adding refrigerant = Total length of piping x quantity of adding refrigerant per metre◆Arrangement : Outer diameter of liquid refrigerant
Checking Correct GroundingIf the power distribution circuit does not have an earth or the ground doesnot comply with specifications, an grounding elec
Setting up Option SwitchesOutdoor Unit PCBYou should display that how many indoor units are connected tothe outdoor unit. Refer to the table below, th
Functions of KEY on the Outdoor Unit PCBKEY FunctionsE-26gSEG1afG1G2bcedSEG2gSEG3afG1G2bcedSEG4DisplayK1 K2 K3 K4KEYCheck mode RESET View modeFunction
Check ModeE-27ENGLISHView ModeIf you press KEY 4, the display shows you temperature and cycle dataaccording to number of times. Refer to the table bel
Checking and Testing OperationsE-28To complete the installation, perform the following checks and tests toensure that the air conditioner is operating
E-29ENGLISHIf both sides numbers are equal, your computer will perform the nextstage.6Check the thermistor sensor, electronic expansion valve by using
E-3 Preparation for Outdoor Unit Installation . . . . . . . . . . 4 Deciding on where to Install the Outdoor Unit . . . . . . 5 Outdoor Unit In
TroubleshootingIf an error occurs during the operation, it is displayed on the outdoor unit PCB. E-30SEG 1, 2SEG 3, 4ExplanationDisplayHigh temperatur
E-31ENGLISHSEG 1, 2SEG 3, 4ExplanationDisplayBreakaway of indoor unit eva sensorBreakaway of indoor unit eva out sensorOpen error of electronic expans
Parts List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33OOOOPPPPTTTTIIIIOOOONNNNAAAALLLLAAAACCCCCCCCEEEESSSSSSSSOOOORRRRIII
Parts ListE-33ENGLISHReceiver & Display Unit AccessoriesReceiver &display unit 1STS 2S-2x10tapped screw 42S-4x12tapped screw2Wire kit(leng
Parts List (cont.)E-34Centralized Controller AccessoriesCentralizedcontroller 1Cable-tie 2Cable clamp5M4x16 tappedscrew7Wiredremote controller1Cable-
MemoE-35ENGLISH
ELECTRONICSTHIS AIR CONDITIONER IS MANUFACTURED BY:ESTE AIRE ACONDICIONADO HA SIDO FABRICADO POR:CE CLIMATISEUR EST FABRIQUE PAR:QUESTO CONDIZIONATORE
E-4Moving the Outdoor Unit by Wire RopeFasten the outdoor unit by two 8m or longer wire ropes asshown at the figure. To protect damage or scratches, i
Deciding on Where to Install the Outdoor UnitE-5ENGLISHOutdoor Unit◆ The outdoor unit must NEVER be placed on its side or upside down, as thecompresso
Deciding on Where to Install the Outdoor Unit (cont.)E-6If there is an obstacle around the outdoor unit...◆ If an obstacle in front of the outdoor uni
Outdoor Unit InstallationE-7ENGLISHFix the outdoor unit with anchor bolts.◆The anchor bolt must be 20mm or higher from the basesurface.NNNNooootttteee
Outdoor Unit Installation (cont.)E-8◆ Make a drain outlet around the base for outdoor unitdrainage.◆ If the outdoor unit is installed on the roof, yo
Connecting the Cable (cont.)E-9ENGLISHPower Cable Specification❋ The power cable is not supplied with air conditioner.IMPORTANT : All power supply ca