Cutting/Flaring the pipesE-10Connect the pipe within 50m and cutting pieces will not be gone into the pipe as being clean to pipe section.Make sure th
ENGLISHE-11Performing leak testsInsulationBefore completing the installation (insulation of the hose and piping), you must check that there are no gas
Drain hose installationCare must be taken when installing the drain hose for the indoor unit toensure that any condensate water is correctly drained o
Testing the drainagePrepare a little water about 5 liters.Pour water into the base pan in the indoor unit as shown in figure.1Confirm that the water f
E-14Connecting the connection cord The indoor unit is powered from the outdoor unit via the connection cord.Remove the screw on the electrical compone
ENGLISHE-151(L)2(N)1(L)2(N)Vc Vc Vw Vw FA FB F1 F2 V1 V2Receiver & Display Unit(Optional)Transmitter(Optional)CentralizedController(Optional)Float
E-16Group control installationK9K10K11K12K9K10K11K12The group control can control 16 rooms(64 indoor units/standard) witha wired controller. When a wh
ENGLISHE-17Before installing the indoor unit, assign an address to the indoor unitaccording to the air conditioning system plan.1The address of the in
E-18Assigning address to indoor unit (Cont.)The MAIN address is for communication between the indoor unit and the outdoorunit. Therefore, you must set
ENGLISHE-19Additional functionsCompensation for lost temperature in heating operation◆ Reduces the difference between an actual room temperature and a
E-2 Parts list . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28OOOOPPPPTTTTIIIIOOOONNNNAAAALLLLAAAACCCCC
Increasing fan speedE-20The vertical axis is the external static pressure(mmAq) while the horizontalaxis represents the AIR FLOW(m3/min).1The characte
Air filter installation (Optional)ENGLISHE-21Remove the air inlet duct flange.1Attach the air filter kit to the air inlet side of indoor unit.2To cle
Drain pump installation (Optional)E-22Open the side of indoor unit.Screw the drain pump with two screws.12Connect the drain hose to the drain socket.3
ENGLISHE-23K1 K2 K3 K4SW03Drain pumpFloat switchCable-tieIndoor unitDrain pump hose portDrain hoseInsulationMust fit tightly against body without any
E-24TroubleshootingDetection of errors◆ If an error occurs during the operation, an LED flickers and the operation is stopped except the LED.◆ If you
ENGLISHE-25LED Display● On Flickering X Off◆If you turn off the air conditioner when the LED is flickering, the LED is also turned off.◆If y
The order of priority : EA → Eb → ox → qx → rx → tx → Ux → vx → Eo - In case that the same error displays from multi-indoor units, the one having t
Parts list . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28OOOOPPPPTTTTIIIIOOOONNNNAAAALLLLAAAACCCCCCCCEEEESSSSSSSSOOOORRRRI
E-28Receiver & Display Unit AccessoriesReceiver &display unit 1STS 2S-2x10tapped screw 42S-4x12tapped screw2Owner’sinstructions1Wire kit (
ENGLISHE-29Centralized Controller AccessoriesCentralizedcontroller 1Cable-tie 2Cable clamp5M4x16 tappedscrew7Transmitter AccessoriesTransmitter com-m
E-3 Preparation for installation . . . . . . . . . . . . . . . . . . . . . 4 Deciding on where to install the indoor unit . . . . . . . . 5 Ind
THIS AIR CONDITIONER IS MANUFACTURED BY:ESTE AIRE ACONDICIONADO HA SIDO FABRICADO POR:CE CLIMATISEUR EST FABRIQUE PAR:QUESTO CONDIZIONATORE D’ARIA È P
E-4Preparation for installationWhen deciding on the location of the air conditioner with the owner,the following restrictions must be taken into accou
ENGLISHE-5Deciding on where to install the indoor unit5mm5mmYou must have 5mm or more space between the ceiling and the bottom of indoor unit.Otherwis
Deciding on where to install the indoor unit (Cont.)E-6Unit : mmDrawing of the indoor unit◆ The inside of ( ) is for HH105/140ECM models.◆ The outsid
Indoor unit installationENGLISHE-71Place the pattern sheet on the ceiling at the spot where you want toinstall the indoor unit.2Insert bolt anchors. U
E-8Purging the unitOn delivery, the indoor unit is loaded with an inert nitrogen gas. All this gas must therefore be purged before connecting the asse
ENGLISHE-9Connecting the indoor unit assembly pipingDrain hose connection portLiquid refrigerantportDrain pump hoseconnection portGas refrigerant port