Increasing fan speed
E-20
The vertical axis is the external static pressure(mmAq) while the horizontal
axis represents the AIR FLOW(m
3
/min).
1
The characteristic curves for ‘HH’, ‘H’, ‘Med’, and ‘Low’ fan speed controller
are shown.
2
The nameplate values are shown based on the ‘H’ air flow.
3
If external static pressure is too great, the air flow volume may drop too
low as explained above.
4
How to Read Diagram
HH : DIP Switch OFF position(High speed)
H : At shipment(Normal speed)
NN
NN
oo
oo
tt
tt
ee
ee
Model
External static pressue(mmAq)
HH105ECM
HH140ECM
HH175ECM
HH175EZM
Min.
8
Normal
14
Max.
20
Range of static pressure
Without air filter
Air Flow (m
3
/min)
10 15 20 25 30 35 40 45
0
5
10
15
20
25
Maximum Air Flow
HH
Minimum Air Flow
Static pressure (mmAq)
Without air filter
Air Flow (m
3
/min)
0
20 25 30 35 40 44
5
10
15
20
25
HH
Static pressure (mmAq)
Without air filter
Air Flow (m
3
/min)
0
15 20 25 30 35 40 45 50 55 60
5
10
15
20
25
Minimum Air Flow
Maximum Air Flow
Static pressure (mmAq)
SW03
K1 K2 K3 K4
K3
ON
OFF
Normal speed
High speed
Switch No.
If external static pressure is too great(due to long extension of ducts, for
example), the air flow volume may drop too low at each air outlet.
This problem can be solved by increasing the fan speed using the following
procedure.
Switch Position Function