Samsung MIM-B17 Installationshandbuch

Stöbern Sie online oder laden Sie Installationshandbuch nach Gateways / Controller Samsung MIM-B17 herunter. Samsung MIM-B17 Installation manual Benutzerhandbuch

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken

Inhaltsverzeichnis

Seite 1 - Air Conditioner

BACnet GatewayMIM-B17Air Conditionerinstallation manualDB98-32390A(3)Eimagine the possibilitiesThank you for purchasing this Samsung product. MIM-B17_

Seite 2 - Safety Precautions

E-10Compatible DevicesNo Devices Model Note1Indoor UnitOutdoor UnitAll System indoor/outdoor unitssuch as: DVM, DVM PLUS, DVM PLUS II, DVM PLUS III,

Seite 3 - Contents

E-11Compatible DevicesDevices Max. NoteIndoor Unit 256 Tracking error occurs if exceededCentralized Controller16 Must not exceed 16 unitsInterface mod

Seite 4 - Checks before installation

E-12Installation plateInstalling the BACnet Gateway 1Separate the installation plate on the rear side of BACnet Gateway.2 Fix the installation plate o

Seite 5 - Accessories

E-13Assistant holewiring grooveInstalling the BACnet Gateway 4 Fix the installation plate and BACnet Gateway using 2 screws. Depending on the instal

Seite 6 - Viewing the Parts

E-14Cable tieLAN cableConnect communication cableAdapterInstalling the BACnet Gateway (Continued)Connecting Centralized Controller1Unfasten the 2 scr

Seite 7

E-15Cable tieLAN cableConnect communication cableAdapterInstalling the BACnet Gateway (Continued)Connecting Interface Module 1Unfasten the 2 screws o

Seite 8 - Product Dimensions

E-16Cable tieLAN cableConnect communication cableAdapterConnecting SIM/PIM1Unfasten the 2 screws on the bottom of the BACnet Gateway front cover. Hol

Seite 9 - System Architecture

E-17Address barSetting the BACnet GatewayBACnet Gateway Connection and Login1Click internet explorer icon( ) twice on your computer.2 When internet ex

Seite 10 - Compatible Devices

E-18Setting the BACnet Gateway (Continued)4 Click [Run] button and continue installation. After installation, access to BACnet Gateway again. Silver

Seite 11

E-19Setting the BACnet Gateway (Continued)55Enter ID and password when BACnet Gateway main web page appears, Then click [LOGIN]. If you click [Connect

Seite 12 - Gateway

E-2 Safety Precautions Read carefully this installation manual before installation and check if the BACnet Gateway is installed correctly after i

Seite 13 - Assistant hole

E-20Setting the BACnet Gateway (Continued)6 If you login successfully, 'Control and Monitoring' screen will appear. Click [System Setting]➔[

Seite 14

E-21Setting the BACnet Gateway (Continued)7 If you access BACnet Gateway, 'Device Configuration' screen will appear initially.  If you cl

Seite 15 - Connecting Interface Module

E-22Reading EHP Watt-hour MeterSetting and checking watt-hour meter1Click [System and Checking Watt-hour meter].  You can change settings on watt-ho

Seite 16 - Connecting SIM/PIM

E-23Reading EHP Watt-hour MeterMonthly baseline setting1Click [System and Checking Watt-hour meter]. 2 Click [Edit] from the ‘Monthly baseline setting

Seite 17 - Setting the BACnet Gateway

E-24Reading EHP Watt-hour Meter (Continued)Period setting1Click [System and Checking Watt-hour meter]. 2 Click [Edit] from the ‘Period setting’ screen

Seite 18

E-25Reading EHP Watt-hour Meter (Continued)Channel setting by indoor unit1Click [Channel setting by indoor unit].2 Click [Edit] from the ‘Channel sett

Seite 19

E-265Check the SIM/PIM interface module channel (Watt-hour meter) information of indoor/outdoor unit.  You can set the channel when SIM/PIM interfac

Seite 20

E-27192.168.0.10006:12:13(AM)MAIN MENU1.IP ConfigAre you sure?YES:Set, NO:Menu1Press [Menu], [], [] or [Set] from the screen where IP and current ti

Seite 21

E-28System SettingsBACnet Gateway network information You can set and check information about BACnet Gateway installation and operation. 1Click [Syst

Seite 22 - Reading EHP Watt-hour Meter

E-29System Settings5When the pop-up window appears, click [OK]. 6If you click [OK], current internet explorer will be closed. Then you may run the web

Seite 23

E-3 Contents Safety PrecautionS ... 2 Before inStalling the Bacnet gateway ...

Seite 24 - Period setting

E-30System Settings (Continued)System time1Click [System Settings].2 Click [Edit] from the 'System time' section.3 Enter system time when te

Seite 25

E-31System Settings (Continued)Selecting the language1Click [System Settings].2 Click [Edit] from the 'Select language' section.3 Select a l

Seite 26

E-32System Settings (Continued)Selecting the contact point control pattern1Click [System Settings].2 Click [Edit] from the 'Select the contact po

Seite 27 - System Setting Initialization

E-33System Settings (Continued)5 When the pop-up window appears, click [OK].  When message with “Reading data from DMS. Please wait” appears savi

Seite 28 - System Settings

E-34System Settings (Continued)PatternControlPattern1▶ No external input (Factory default setting)When you input contact control signal in port 1,

Seite 29

E-35System Settings (Continued) Pattern 2 (May be used for connection with a fire sensor)CH1CH2BACnet GatewayCH1CH2BACnet Gateway CH1CH2BACnet Gatew

Seite 30 - System Settings (Continued)

E-36BACnet gateway information1Click [System Settings].2 You can check the basic BACnet gateway information from 'BACnet gateway information&apos

Seite 31

E-37  What is tracking?Tracking is an operation that finds devices connected to BACnet Gateway. Through tracking operation, devices will be recogn

Seite 32

E-38Tracking (Continued)Setting communication mode for each channel1Click [Device Configuration].2 Click [Edit] from the 'Communication mode by c

Seite 33

E-39Tracking (Continued)3When each channel is enabled, check the communication mode you want to set for each channel.  You cannot change the commun

Seite 34

E-4Checks before installation1BACnet Gateway IP A public IP is needed to access the BACnet Gateway over the internet. (One public IP is needed for e

Seite 35

E-40Tracking (Continued)DVM Tracking1Click [Device Configuration].2 Click [DVM Tracking].12MIM-B17_BACnet Gateway_IM_E 32390-3.indd 40 2011-04-04

Seite 36

E-41Tracking (Continued)3Enter administrator’s password.4Click [OK].5When tracking information window pops up, check it and click [OK] to continue.

Seite 37 - Tracking

E-42Tracking (Continued)7Message will appear to alert that tracking is completed. Select the zone initializing mode and click [OK].  No initializa

Seite 38 - Tracking (Continued)

E-43Disconnect all devices1Click [Device Configuration].2Click [Disconnect all devices].3Enter administrator’s password.4Click [OK].Device Configurati

Seite 39

E-44Device Configuration (Continued)5When the information window pops up, you must check the information and click [OK] to continue.6When message with

Seite 40

E-45Device Configuration (Continued)1From the list of devices searched by tracking, click [Edit] in the bottom of the list.  [Edit] will be changed

Seite 41

E-46Device Configuration (Continued)2Enter the name of the devices when the text box enables.  You cannot use special characters within the device na

Seite 42

E-47Device Configuration (Continued)1Click one of the Object ID from 'Object ID' column. Detail information of the selected device will be d

Seite 43 - Device Configuration

E-48Device Configuration (Continued)2Analog data of the selected device will be displayed in Analog data.  Object ID: Displays ID of the correspondi

Seite 44

E-49Device Configuration (Continued)6Binary data of the selected device will be displayed in Binary data.  Object ID: Displays ID of the correspond

Seite 45 - Renaming the devices

E-5ItemBACnet Gateway Quantity 1ShapeAdapter Power cable M4x16 Screw11 6User’s manualInstallation manualCable tie1 1 1Make sure you have each item. Su

Seite 46

E-5010Multi-state Data of the selected device will be displayed in Multi-state data.  Object ID: Displays ID of the corresponding object.  Type:

Seite 47 - Checking device information

E-51BACnet Protocol Implementation Conformance StatementDate: May 24. 2010 Vendor Name: SAMSUNG Electronics CO., Ltd.

Seite 48

E-52BACnet Protocol Implementation Conformance Statement (Continued)SUPPORTED BIBBSBIBB NAMESUPPORTED REMARKSAlarm and Event ManagementAE-N-A Alarm&a

Seite 49

E-53BACnet Protocol Implementation Conformance Statement (Continued)SUPPORTED BIBBSBIBB NAMESUPPORTED REMARKSDevice and Network ManagementDM-R-A Resta

Seite 50

E-54BACnet Protocol Implementation Conformance Statement (Continued)Data Link Layer Options: BACnet IP, (Annex J)  BACnet IP, (Annex J), Foreign Dev

Seite 51

E-55Standard Object Types SupportedObject Type SupportDescriptionAnalog Input[Indoor temperature], [The power value after the basic date], [The numb

Seite 52

E-56DeviceFollowing table shows regulation of device ID and they are created automatically.Refer to BACnet point ListDNET (Gateway number)Centralized

Seite 53 - Multi-state Value

E-57Indoor UnitSingle indoor unit has following point list. Instance NumberObjectObject TypeObject NameUnit Status value InactiveActiveText-1 Text-2 T

Seite 54

E-58BACnet Point List (Continued)Single AHU unit has following point list.Instance NumberObjectObject TypeObject NameUnit Status value InactiveActiveT

Seite 55

E-59BACnet Point ListSingle ERV unit has following point list.Instance NumberObjectObject TypeObject Name Status value1 SIM error code AI SIM_Error_Co

Seite 56 - 9 417 32

E-6BACnet Gateway ExteriorLCD Display Shows current time and IP address. Various messages will be displayed depending on button input.LCD operation bu

Seite 57 - BACnet Point List

E-60 You may use ALL_OFF command to turn on all the indoor units but it is not recommended.  If communication error occurs on devices such as S

Seite 58 - BACnet Point List (Continued)

E-61Other InformationObject setting when there is general errorIf any air conditioner related error occurs, the property will be set as below.1. The R

Seite 59

E-62 MemoMIM-B17_BACnet Gateway_IM_E 32390-3.indd 62 2011-04-04 오후 3:44:31

Seite 60

E-63 MemoMIM-B17_BACnet Gateway_IM_E 32390-3.indd 63 2011-04-04 오후 3:44:31

Seite 61 - Other Information

MIM-B17_BACnet Gateway_IM_E 32390-3.indd 64 2011-04-04 오후 3:44:31

Seite 62

E-7Name DescriptionDI Terminal1 Digital Input connection terminal, Channel1~Channel5DI Terminal2 Digital Input connection terminal, Channel6~Channel10

Seite 63

E-8 24025564.80(Unit : mm)Display Board40-pin Cable20-pin CableMain BoardSub BoardBACnet Gateway InteriorMain PartsViewing the Parts (Continued)Note

Seite 64

E-9  Connecting centralized controller and BACnet Gateway ( type) - You can control up to 16 centralized controllers and 256 indoor units using B

Kommentare zu diesen Handbüchern

Keine Kommentare