BACnet GatewayMIM-B17Air Conditionerinstallation manualDB98-32390A(3)Eimagine the possibilitiesThank you for purchasing this Samsung product. MIM-B17_
E-10Compatible DevicesNo Devices Model Note1Indoor UnitOutdoor UnitAll System indoor/outdoor unitssuch as: DVM, DVM PLUS, DVM PLUS II, DVM PLUS III,
E-11Compatible DevicesDevices Max. NoteIndoor Unit 256 Tracking error occurs if exceededCentralized Controller16 Must not exceed 16 unitsInterface mod
E-12Installation plateInstalling the BACnet Gateway 1Separate the installation plate on the rear side of BACnet Gateway.2 Fix the installation plate o
E-13Assistant holewiring grooveInstalling the BACnet Gateway 4 Fix the installation plate and BACnet Gateway using 2 screws. Depending on the instal
E-14Cable tieLAN cableConnect communication cableAdapterInstalling the BACnet Gateway (Continued)Connecting Centralized Controller1Unfasten the 2 scr
E-15Cable tieLAN cableConnect communication cableAdapterInstalling the BACnet Gateway (Continued)Connecting Interface Module 1Unfasten the 2 screws o
E-16Cable tieLAN cableConnect communication cableAdapterConnecting SIM/PIM1Unfasten the 2 screws on the bottom of the BACnet Gateway front cover. Hol
E-17Address barSetting the BACnet GatewayBACnet Gateway Connection and Login1Click internet explorer icon( ) twice on your computer.2 When internet ex
E-18Setting the BACnet Gateway (Continued)4 Click [Run] button and continue installation. After installation, access to BACnet Gateway again. Silver
E-19Setting the BACnet Gateway (Continued)55Enter ID and password when BACnet Gateway main web page appears, Then click [LOGIN]. If you click [Connect
E-2 Safety Precautions Read carefully this installation manual before installation and check if the BACnet Gateway is installed correctly after i
E-20Setting the BACnet Gateway (Continued)6 If you login successfully, 'Control and Monitoring' screen will appear. Click [System Setting]➔[
E-21Setting the BACnet Gateway (Continued)7 If you access BACnet Gateway, 'Device Configuration' screen will appear initially. If you cl
E-22Reading EHP Watt-hour MeterSetting and checking watt-hour meter1Click [System and Checking Watt-hour meter]. You can change settings on watt-ho
E-23Reading EHP Watt-hour MeterMonthly baseline setting1Click [System and Checking Watt-hour meter]. 2 Click [Edit] from the ‘Monthly baseline setting
E-24Reading EHP Watt-hour Meter (Continued)Period setting1Click [System and Checking Watt-hour meter]. 2 Click [Edit] from the ‘Period setting’ screen
E-25Reading EHP Watt-hour Meter (Continued)Channel setting by indoor unit1Click [Channel setting by indoor unit].2 Click [Edit] from the ‘Channel sett
E-265Check the SIM/PIM interface module channel (Watt-hour meter) information of indoor/outdoor unit. You can set the channel when SIM/PIM interfac
E-27192.168.0.10006:12:13(AM)MAIN MENU1.IP ConfigAre you sure?YES:Set, NO:Menu1Press [Menu], [], [] or [Set] from the screen where IP and current ti
E-28System SettingsBACnet Gateway network information You can set and check information about BACnet Gateway installation and operation. 1Click [Syst
E-29System Settings5When the pop-up window appears, click [OK]. 6If you click [OK], current internet explorer will be closed. Then you may run the web
E-3 Contents Safety PrecautionS ... 2 Before inStalling the Bacnet gateway ...
E-30System Settings (Continued)System time1Click [System Settings].2 Click [Edit] from the 'System time' section.3 Enter system time when te
E-31System Settings (Continued)Selecting the language1Click [System Settings].2 Click [Edit] from the 'Select language' section.3 Select a l
E-32System Settings (Continued)Selecting the contact point control pattern1Click [System Settings].2 Click [Edit] from the 'Select the contact po
E-33System Settings (Continued)5 When the pop-up window appears, click [OK]. When message with “Reading data from DMS. Please wait” appears savi
E-34System Settings (Continued)PatternControlPattern1▶ No external input (Factory default setting)When you input contact control signal in port 1,
E-35System Settings (Continued) Pattern 2 (May be used for connection with a fire sensor)CH1CH2BACnet GatewayCH1CH2BACnet Gateway CH1CH2BACnet Gatew
E-36BACnet gateway information1Click [System Settings].2 You can check the basic BACnet gateway information from 'BACnet gateway information&apos
E-37 What is tracking?Tracking is an operation that finds devices connected to BACnet Gateway. Through tracking operation, devices will be recogn
E-38Tracking (Continued)Setting communication mode for each channel1Click [Device Configuration].2 Click [Edit] from the 'Communication mode by c
E-39Tracking (Continued)3When each channel is enabled, check the communication mode you want to set for each channel. You cannot change the commun
E-4Checks before installation1BACnet Gateway IP A public IP is needed to access the BACnet Gateway over the internet. (One public IP is needed for e
E-40Tracking (Continued)DVM Tracking1Click [Device Configuration].2 Click [DVM Tracking].12MIM-B17_BACnet Gateway_IM_E 32390-3.indd 40 2011-04-04
E-41Tracking (Continued)3Enter administrator’s password.4Click [OK].5When tracking information window pops up, check it and click [OK] to continue.
E-42Tracking (Continued)7Message will appear to alert that tracking is completed. Select the zone initializing mode and click [OK]. No initializa
E-43Disconnect all devices1Click [Device Configuration].2Click [Disconnect all devices].3Enter administrator’s password.4Click [OK].Device Configurati
E-44Device Configuration (Continued)5When the information window pops up, you must check the information and click [OK] to continue.6When message with
E-45Device Configuration (Continued)1From the list of devices searched by tracking, click [Edit] in the bottom of the list. [Edit] will be changed
E-46Device Configuration (Continued)2Enter the name of the devices when the text box enables. You cannot use special characters within the device na
E-47Device Configuration (Continued)1Click one of the Object ID from 'Object ID' column. Detail information of the selected device will be d
E-48Device Configuration (Continued)2Analog data of the selected device will be displayed in Analog data. Object ID: Displays ID of the correspondi
E-49Device Configuration (Continued)6Binary data of the selected device will be displayed in Binary data. Object ID: Displays ID of the correspond
E-5ItemBACnet Gateway Quantity 1ShapeAdapter Power cable M4x16 Screw11 6User’s manualInstallation manualCable tie1 1 1Make sure you have each item. Su
E-5010Multi-state Data of the selected device will be displayed in Multi-state data. Object ID: Displays ID of the corresponding object. Type:
E-51BACnet Protocol Implementation Conformance StatementDate: May 24. 2010 Vendor Name: SAMSUNG Electronics CO., Ltd.
E-52BACnet Protocol Implementation Conformance Statement (Continued)SUPPORTED BIBBSBIBB NAMESUPPORTED REMARKSAlarm and Event ManagementAE-N-A Alarm&a
E-53BACnet Protocol Implementation Conformance Statement (Continued)SUPPORTED BIBBSBIBB NAMESUPPORTED REMARKSDevice and Network ManagementDM-R-A Resta
E-54BACnet Protocol Implementation Conformance Statement (Continued)Data Link Layer Options: BACnet IP, (Annex J) BACnet IP, (Annex J), Foreign Dev
E-55Standard Object Types SupportedObject Type SupportDescriptionAnalog Input[Indoor temperature], [The power value after the basic date], [The numb
E-56DeviceFollowing table shows regulation of device ID and they are created automatically.Refer to BACnet point ListDNET (Gateway number)Centralized
E-57Indoor UnitSingle indoor unit has following point list. Instance NumberObjectObject TypeObject NameUnit Status value InactiveActiveText-1 Text-2 T
E-58BACnet Point List (Continued)Single AHU unit has following point list.Instance NumberObjectObject TypeObject NameUnit Status value InactiveActiveT
E-59BACnet Point ListSingle ERV unit has following point list.Instance NumberObjectObject TypeObject Name Status value1 SIM error code AI SIM_Error_Co
E-6BACnet Gateway ExteriorLCD Display Shows current time and IP address. Various messages will be displayed depending on button input.LCD operation bu
E-60 You may use ALL_OFF command to turn on all the indoor units but it is not recommended. If communication error occurs on devices such as S
E-61Other InformationObject setting when there is general errorIf any air conditioner related error occurs, the property will be set as below.1. The R
E-62 MemoMIM-B17_BACnet Gateway_IM_E 32390-3.indd 62 2011-04-04 오후 3:44:31
E-63 MemoMIM-B17_BACnet Gateway_IM_E 32390-3.indd 63 2011-04-04 오후 3:44:31
MIM-B17_BACnet Gateway_IM_E 32390-3.indd 64 2011-04-04 오후 3:44:31
E-7Name DescriptionDI Terminal1 Digital Input connection terminal, Channel1~Channel5DI Terminal2 Digital Input connection terminal, Channel6~Channel10
E-8 24025564.80(Unit : mm)Display Board40-pin Cable20-pin CableMain BoardSub BoardBACnet Gateway InteriorMain PartsViewing the Parts (Continued)Note
E-9 Connecting centralized controller and BACnet Gateway ( type) - You can control up to 16 centralized controllers and 256 indoor units using B