E-9Display Board40-pin Cable20-pin CableDI contact control option switchMain BoardSub BoardDMS2 InteriorMain PartsViewing the Parts (Continued)Note
E-99LonWorks Gateway Setting (Continued)DescriptionSetting/monitoring upper limit temperature and function toggleSNVT Type SNVT_switch: Unsigned/signe
E-100DescriptionFilter alert resetSNVT Type SNVT_switch: Unsigned/singed ShortValue and operationValue State Operation remark0.0 0 No Action100.0 1 Fi
E-101LonWorks Gateway Setting (Continued)desription character valueascii.[0] Model informationAlphabet or digitAlphabet or digitAlphabet or digitAlpha
E-102Data for DMS SystemDescriptionDigital output status on DMSSNVT Type SNVT_switch: Unsigned/singed ShortValue and operationValue StateOFF 0.0 0ON 1
E-103LonWorks Gateway Setting (Continued)DescriptionSIM/PIM Communication Error CodeSNVT TypeSNVT_count: Unsigned Long, 2 bytesValue and operationSIM/
E-104Configuration PropertiesDetails of Configuration PropertiesThis document provides information on all configuration properties defined for LonWork
E-105LonWorks Gateway Setting (Continued)Recommendations If required, set a value greater than the default update rate (currently, 10s). Any smaller v
E-106SpecificationsItems DescriptionExteriorSize 240 X 255 X 64.8 mm ( Width X Length X Height )Weight 1.48 KgPowerSource DC ADAPTORINPUT Voltage 100-
E-107LicenseOpen Source AnnouncementOpen Source AnnouncementThe software included in this product contains open source software. You may obtain the co
E-10 Connecting centralized controller and DMS2 ( type)- You can control up to 16 centralized controllers and 256 indoor units using DMS2. Conne
E-11Compatible DevicesNo Devices Model Note1Indoor UnitOutdoor UnitAll System indoor/outdoor unitssuch as: DVM, DVM PLUS, DVM PLUS II, DVM PLUS III,
E-12Devices Max. NoteIndoor Unit 256 Tracking error occurs if exceededCentralized Controller16 Must not exceed 16 unitsInterface module25616 units per
E-13Installation plateInstalling the DMS21Separate the installation plate on the rear side of DMS2.2 Fix the installation plate on the wall using 4 sc
E-14Assistant holewiring groove4 Fix the installation plate and DMS2 using 2 screws. Depending on the installation environment, fix DMS2 using assis
E-15Cable tieLAN cableConnect communication cableAdapterInstalling the DMS2 (Continued)Connecting Centralized Controller1Unfasten the 2 screws on the
E-16Cable tieLAN cableConnect communication cableAdapterConnecting Interface Module 1Unfasten the 2 screws on the bottom of the DMS2 front cover. Hol
E-17Installing the DMS2 (Continued)Cable tieLAN cableConnect communication cableAdapterConnecting SIM1Unfasten the 2 screws on the bottom of the DMS2
E-18 You can set the system settings through contact control pattern.Setting the External Contact Control PatternUsing the DI External Contact Contr
DMS2(Data Management Server2)MIM-D00ABACnet GatewayMIM-B17LonWorks GatewayMIM-B18 Air Conditioneruser & installation manual DB98-32138A-10ENimagi
E-19Using the DI External Contact Control (Optional)Installing the DMS2 (Continued)PatternControlPattern1▶ No external input (Factory default setti
E-20 Pattern 2 (May be used for connection with a fire sensor)CH1CH2DMS2 CH1CH2DMS2 CH1CH2DMS2 Pattern 3 (External contact signal control) Pat
E-21Cross cableDMS2S-NET3LAN cableDMS2S-NET3HUBSetting the Computer Environment1Device related to network (Purchase separately) Computer with a LAN
E-22 IP address : 192.168.0.1(~253) Except 100 Subnet mask : 255.255.255.0 Default gateway : 192.168.0.1Setting the Computer Environment (Conti
E-23 IP address : 192.168.0.1(~253) Except 100 Subnet mask : 255.255.255.0 Default gateway : 192.168.0.1Address barSetting the DMS2DMS2 Connect
E-24Setting the DMS2 (Continued)4 Click [Run] button and continue installation. After installation, access DMS2 again. Silverlight operates normall
E-25Setting the DMS2 (Continued)5Enter ID and password when DMS2 main web page appears. Then click [LOGIN]. Depending on authorization settings set
E-26Setting the DMS2 (Continued)DMS2 System Environment Setting (Network settings) You can set and check information about DMS2 installation operat
E-27Setting the DMS2 (Continued)Note Factory setting is as follows. - IP address: 192.168.0.100 - Subnet mask address: 255.255.255.0 - De
E-28System Time Setting Setting the DMS2 (Continued)1Select [System Settings] menu and click [System environment setting].2 Click [Edit] from system t
E-2 Safety Precautions Do not attempt to install or repair the product by yourself. The product contains no user-serviceable parts. Always consult
E-29Setting the DMS2 (Continued)Setting the Language1Select [System Settings] menu and click [System environment setting].2 Click [Edit] from language
E-30DMS2 Name SettingSetting the DMS2 (Continued)1Select [System Settings] menu and click [System environment setting].2 Click [Edit] from DMS2 name s
E-31Setting the DMS2 (Continued)Error Mail Forwarding Setting 1Select [System Settings] menu and click [System environment setting].2 Click [Edit] fro
E-32Setting the DMS2 (Continued)Setting Enable public IP1Select [System Settings] menu and click [System environment setting].2 Click [Edit] on Enable
E-33192.168.0.10006:12:13(AM)MAIN MENU1.IP ConfigAre you sure?YES:Set, NO:MenuSetting the DMS2 (Continued)System setting initialization1Press [Menu],
E-34 What is tracking?Tracking is an operation that finds devices which are connected to DMS2. Through tracking operation, devices which are conn
E-35TrackingSetting Communication Mode for Each Channel1Select [System Settings] menu and click [Tracking].2Click [Edit] from communication mode for e
E-36DVM Tracking1Select [System Settings] menu and click [Tracking].2Click [DVM Tracking]. 3Enter administrator’s password and then click [OK].4Tracki
E-37Tracking (Continued)7Page will be refreshed by clicking [OK]. Then you can check tracking result. Note If tracking is executed successfully whe
E-38Disconnect All DevicesFunctionInitialize searched device status in DMS2. Monitoring and controlling of all the connected devices to DMS2 will be
E-3 Read carefully this user & installation manual before installation and check if the product is installed correctly after installation.
E-39Disconnect All DevicesTracking (Continued)Renaming the Device1Select [System Settings] menu and click [Tracking].2Click [Edit] on the bottom of tr
E-40DMS DI•DO Port Setting1Select [System Settings] and then click [Tracking].2Click [Setting] which is next to DMS DI•DO of device list.3Click [Edit]
E-41Tracking (Continued)PIM Setting1Click [System Settings] [Tracking] when DMS2 web page menu screen appears.2Click [Setting] which is next to PIM
E-42Channel Setting by Indoor Unit1Click [EHP Power Consumption Inspection] [Channel setting by indoor unit] when DMS2 web page menu screen appears.
E-434Check the information of indoor/outdoor unit which is connected to watt-hour meter.5Check the SIM/PIM channel(watt-hour meter) information of in
E-446Check the virtual channel information of indoor/outdoor unit. To execute power distribution without SIM/PIM, you should set virtual channel.
E-45 1. Public IP : Ordinary IP used to connect internet is called public IP.1-1. Static IP : Static IP is a number that is assigned to a comput
E-46Examples of DMS2 Installation with DSLLocal Management without External Control : Use Private IP Direct connection between DMS2 and computer or
E-47ComputerComputer cannot distinguish which DMS2 has 192.168.0.100 IP. DMS2 ①Initial IP : 192.168.0.100DMS2 ②Initial IP : 192.168.0.100DMS2 ③Initi
E-48 Connecting centralized controller and BACnet Gateway ( type) - You can control up to 16 centralized controllers and 256 indoor units using
E-4 Contents Safety PrecautionS ... 2 Before inStalling the DMS2 ...
E-49BACnet Gateway settingNo Devices Model Note1Indoor UnitOutdoor UnitSystem indoor/outdoor unitssuch as: DVM, DVM PLUS, DVM PLUS II, DVM PLUS III,
E-50Devices Max. NoteIndoor Unit 256 Tracking error occurs if exceededCentralized Controller16 Must not exceed 16 unitsInterface module25616 units per
E-51BACnet Gateway setting (Continued)Setting the BACnet Gateway1Click internet explorer icon( ) twice on your computer.2When internet explorer window
E-525Enter ID and password when BACnet Gateway main web page appears, Then click [LOGIN]. If you use accounts with general authorization level to
E-53BACnet Gateway setting (Continued)6If you login successfully, ‘Control and Monitoring’ screenwill appear.Click [System Settings] [BACnet configu
E-54Reading EHP Watt-hour Meter1Click [System and Checking Watt-hour meter]. You can change settings on watt-hour meter only when SIM/PIM interface
E-55Reading EHP Watt-hour MeterBACnet Gateway setting (Continued)1Click [System and Checking Watt-hour meter]. 2Click [Edit] from the ‘Monthly baselin
E-561Click [System and Checking Watt-hour meter]. 2Click [Edit] from the ‘Period setting’ screen. You can select checkbox to set period in daily
E-57BACnet Gateway setting (Continued)System Settings You can set and check information about BACnet Gateway installation and operation. 1Click [Syst
E-581Click [System Settings].2You can check the basic BACnet gateway information from 'BACnet gateway information' section.3Click [Edit] fro
E-5Checks before installation1DMS2 IP Basically, only Private IP can be set to IP address. To use Public IP, you must set Enable public IP as ‘Enabl
E-59BACnet Gateway setting (Continued)Device Configuration1Click one of the Object ID from ‘Object ID’ column.Detail information of the selected devic
E-606Binary data of the selected device will be displayed in Binary data. Object ID: Displays ID of the corresponding object. Type: Displays t
E-61BACnet Gateway setting (Continued)11You can select the values to modify the Output type objects. Click [Edit] button on the bottom of the 'De
E-62Date: 2012. 10. 31 Vendor Name: SAMSUNG Electronics CO., Ltd.
E-63BACnet Gateway setting (Continued)SUPPORTED BIBBSBIBB NAMESUPPORTED REMARKSAlarm and Event ManagementAE-N-A Alarm&Event-Notication-AAE-N-I-
E-64SUPPORTED BIBBSBIBB NAMESUPPORTED REMARKSDevice and Network Manage-mentDM-R-A Restart-ADM-R-B Restart-BDM-LM-A List Manipulation-ADM-LM-B List
E-65BACnet Gateway setting (Continued)Data Link Layer Options: BACnet IP, (Annex J) BACnet IP, (Annex J), Foreign Device ISO 8802-3, Ethernet (
E-66Detail Description of ObjectFollowing table shows regulation of device ID and they are created automatically.Refer to BACnet point ListEx) Indoor
E-67BACnet Gateway setting (Continued)BACnet Point ListSingle indoor unit has following point list. Instance NumberObjectObject TypeObject NameUnit St
E-68Instance NumberObjectObject TypeObject NameUnit Status value InactiveActiveText-1 Text-2 Text-3 Text-4 Text-513 Filter sign reset BOAC_FilterSign_
E-6Item DMS2 Quantity 1ShapeAdapter Power cable M4x16 Screw11 6User & installation manualCable tie1 1Make sure you have each item. Supplied items
E-69BACnet Gateway setting (Continued)Single AHU unit has following point list.Instance NumberObjectObject TypeObject NameUnit Status value InactiveAc
E-70Single EHS Unit has following point list.Instance NumberObjectObject TypeObject NameUnit Status value InactiveActiveText-1 Text-2 Text-3 Text-41 R
E-71BACnet Gateway setting (Continued)Single ERV unit has following point list.Instance NumberObjectObject TypeObject NameUnit Status value InactiveAc
E-72Single Centralized controller has following point list.Instance NumberObjectObject TypeObject Name Status value1Centralized controller error codeA
E-73BACnet Gateway setting (Continued)Instance NumberObjectObject TypeObject NameUnit Status value InactiveActiveText-1 Text-2 Text-3 Text-4 Text-51 O
E-74DDC has following point list. If communication error occurs on devices such as SIM/Centralized Controller/Interface Module etc, other functions
E-75BACnet Gateway setting (Continued)Other InformationCOV registration information will disapper when a BACnet gateway is switched o. The reserved v
E-76Viewing LonWorks Gateway’s PartsLonWorks Gateway ExteriorLCD Display Shows current time and IP address. Various messages will be displayed dependi
E-77Viewing LonWorks Gateway’s PartsName DescriptionDI Terminal1 Digital Input connection terminal, Channel1~Channel5DI Terminal2 Digital Input connec
E-78 24025564.80(Unit : mm)Display Board40-pin Cable20-pin CableMain BoardLonWorks Board10-pin Cable2-pin CableSub BoardLonWorks Gateway InteriorMain
E-7DMS2 ExteriorLCD Display Shows current time and IP address. Various messages will be displayed depending on button input.LCD operation button Ther
E-79LonWorks Gateway SettingCentralized controllerLonWorks GatewayTP/FT-10BMS systemBMS EngineeringSAMSUNG EngineeringInterface moduleInterface module
E-80No Devices Model Note1Indoor UnitOutdoor UnitAll System indoor/outdoor unitssuch as: DVM, DVM PLUS, DVM PLUS II, DVM PLUS III, mini DVM, CAC Ser
E-81LonWorks Gateway Setting (Continued)Devices Max. NoteIndoor Unit 128 Tracking error occurs if exceededCentralized Controller16 Must not exceed 16
E-82Installing the LonWorks GatewayCommisionTo activate the Service Pin, press and hold [SET] button for more than three seconds while time is display
E-83LonWorks Gateway Setting (Continued)Control and Monitoring ItemThe functions provided can be different according to the type of the connected devi
E-84 Although the LonWorks Gateway can connect 128 units, the actual number of available items can differ according to the number of indoor units
E-85LonWorks Gateway Setting (Continued)Setting the LonWorks Gateway1Click internet explorer icon( ) twice on your computer.2When internet explorer wi
E-865Enter ID and password when LonWorks Gateway main web page appears, Then click [LOGIN]. If you click [Connect], you will be logged in with general
E-87LonWorks Gateway Setting (Continued)6If you login successfully, 'Control and Monitoring' screen of DMS2 will appear. Click [System Setti
E-881Click [Setting and Checking Watt-hour meter]. 2Click [Edit] from the ‘Monthly baseline setting’ screen. You can make changes when list box ena
E-8Name DescriptionDI Terminal1 Digital Input connection terminal, Channel1~Channel5DI Terminal2 Digital Input connection terminal, Channel6~Channel10
E-89Reading EHP Watt-hour MeterLonWorks Gateway Setting (Continued)1Click [Setting and Checking Watt-hour meter]. 2Click [Edit] from the ‘Period setti
E-901Device Type, Address, Name and Object ID will appear. 2Object IDs are assigned in order from 1 to 128 when initial tracking is executed.3If you w
E-91LonWorks Gateway Setting (Continued)1Click one of the Addresses from ‘Address’ colum. Detail information of the selected device will be displaye
E-92No. NV Name NV TypeRemarks1nviOnO SNVT_switch ON/OFF command2nviApplicMode SNVT_hvac_mode Setting operating mode3nviSetpoint SNVT_temp_p Setting
E-93LonWorks Gateway Setting (Continued)No. NV Name NV Type Remarks1 nviDigitalOut[6] SNVT_ switch Control Digital output of DMS2 nviAllO SNVT_hvac_e
E-94Network Parameter ChartSSACIndoor[nn](object id = 1-128)nvoSpaceTemp SNVT_temp_pnviSetPoint SNVT_temp_pnvoCoolTempLock SNVT_switchnviUserLockout S
E-95LonWorks Gateway Setting (Continued)SSACSystem(object id = 129)nvoDigitalOut[6] SNVT_switchnvoDigitalIn[8] SNVT_switchnvoSystemLock SNVT_switchnvo
E-96Message DefinitionDescriptionIndoor temperatureSNVT Type SNVT_temp_p: Signed Long, 2 bytesValue and operationRange: -10.00°C ~ 50.00°C nvoSpaceT
E-97LonWorks Gateway Setting (Continued)DescriptionFan Speed and directionSNVT Type SNVT_switch: Unsigned/signed ShortValue and operationValue StateAu
E-98Description1. Remote control restriction status2. Filter alert status3. Thermo On/Off status4. Error alert StatusSNVT Type SNVT_state: 16 Unsigned