E-60
You may use ALL_OFF command to turn on all the indoor units but it is not
recommended.
If communication error occurs on devices such as SIM/Centralized Controller/
Interface Module etc, other functions such as power distribution may also
create a problem. You must have BMS system to check the errors and you must
take action immediately.
BACnet Point List (Continued)
Single Centralized controller has following point list.
Instance
Number
Object
Object
Type
Object Name Status value
1
Centralized controller error
code
AI
Central_Error_
Code
Refer to the list of the
integrated error code
Centralized controller
Instance
Number
Object
Object
Type
Object Name Status value
1 Interface module error code AI
Repeater_Error_
Code
Refer to the list of the
integrated error code
Single Interface module has following point list.
Interface module
Instance Control and Monitoring
Object
Type
Object Name Status Value
1 All device OFF BO ALL_OFF Inactive : All devices O
2 DMS2 Status AI DMS2_Status
0: Normal, 8: Emergency
stop, 105 : Tracking in
progress, 108 : Tracking
failed
3 BACnet error code AI
BACnetApp_
Error_Code
BACnet error code
BACnet Gateway has following point list.
BACnet Gateway