BACnet Point List
Single ERV unit has following point list.
Instance
Number
Object
Object
Type
Object Name Status value
1 SIM error code AI SIM_Error_Code Refer to list of error code
Instance
Number
Object
Object
Type
Object Name
Unit Status value
Inactive
Active
Text-1 Text-2 Text-3 Text-4 Text-5
1 Power On/O operation BV ERV_Power_xx_xxxxxx Off ON
2 Filter sign status BI
ERV_FilterSign_xx_
xxxxxx
Off ON
3 Filter sign reset BO
ERV_FilterSign_Reset_
xx_xxxxxx
Off ON
4 Operation mode status MV
ERV_Operation_
Mode_xx_xxxxxx
Auto HeatEx Bypass Sleep
5 Fan speed status MV
ERV_FanSpeed_xx_
xxxxxx
Low High Turbo
6
Remote controller limit
status
MV
ERV_Remocon_Limit_
xx_xxxxxx
Work
Fully
Limited
Power
On
Limited
7
Integrated error code of
ERV unit
AI
ERV_Error_Code_xx_
xxxxxx
Refer to list of error code
ERV