BACnet Gateway setting (Continued)
Other Information
COV registration information will disapper when a BACnet
gateway is switched o. The reserved value caused by the
power supply problem is not guaranteed according to the
BACnet regulation.
If any communication error occurs between the air conditioner
devices, the property will be set as below.
1. Reliability property will be set as COMMUNICATION_FAILURE.
2. Fault / Alarm flag of Status_Flags property will be set as
TRUE.
3. Present_Value property is readable but the value is not
guaranteed.
Object setting when there is communication error
If any air conditioner related error occurs, the property will be
set as below.
1. The Reliability property value of each object will be set as
UNRELIABLE_OTHER.
2. FAULT / Alarm flag of Status Flags property will be set as
TRUE.
Object setting when there is general error
Time setting
Time synchronization Service is a service that allows the time of
BACnet Gateway to be synchronized with the time of PC.
COV (Change Of Value)
COV service is supported and you can set confirmed or uncon-
firmed COV.
You can set lifetime value.
Main service
SOL_DMS2&BAC&LW_IBIM_EN_32138A-10_EN_150617.indd 75 2015-06-18 오후 5:34:20