E-83
LonWorks Gateway Setting (Continued)
Control and Monitoring Item
The functions provided can be different according to the type of the connected device.
Functional classification by a device.
No NV Name
Remarks Indoor ERV AHU Kit
1
nviOnO ON/OFF command O O O
2
nviApplicMode Setting operating mode O X O
3
nviSetpoint Setting desirable temperature O X O
4
nviFanStatus Setting wind speed and direction O O X
5
nviERVMode Setting ERV operation mode X O X
6
nviFilterReset Filter reset command O O O
7
nviUserLockout Setting the restriction of remote control use O O O
8
nviOccOpMode
Setting cooling only mode / Setting heating
only mode
O X O
9
nviCoolTempLock Setting the low temperature limit O X O
10
nviHeatTempLock Setting the high temperature limit O X O
11
nvoSpaceTemp Display indoor temperature O X O
12
nvoApplicMode Display operating mode O X O
13
nvoSetpoint Display desire temperature O X O
14
nvoOnOff Display ON/OFF status O O O
15
nvoFanStatus Display wind speed and direction O O X
16
nvoERVMode Display ERV operating mode X O X
17
nvoErrorCode Display Error code O O O
18
nvoDeviceAlarm
Remote control Lock, Filter Sign, Thermo
ON/OFF, Error occurrence status display
O O O
19
nvoOccOpMode
Cooling only/Heating only setup status
display
O X O
20
nvoCoolTempLock Low temperature limit setting status display O X O
21
nvoHeatTempLock High temperature limit setting status display O X O
22
nvoUserLockout Display the restriction of remote control use O O O
23
nvoEnergyConp Display electricity usage (Time Period) O X X
24
nvoEnergyCon Display electricity usage (Basic date) O X X
25
nvoRuntimep Display used hours (Period) O X O
26
nvoRuntime Display used hours (Basic date) O X O
27
nvoDevListDesc
The summary of device information
(Model, Address, Operation Status)
O O O
SOL_DMS2&BAC&LW_IBIM_EN_32138A-10_EN_150617.indd 83 2015-06-18 오후 5:34:28