5. Outdoor Units installation
134
12. Pump-Out Procedure
1) General Instructions
(1) Pump-out is the name of operation which pumps out the refrigerant from outdoor unit.
(2) Pump out operation can be put into operation with more than 2 outdoor units installed.
(3) If system is under extremely low pressure, compressor will be damaged. When low pressure go
down 2kgf/㎠ or below, close the service valve quickly.
2) Procedure of Pump down operation
Close Liquid SVC Valve of
outdoor unit to carry out pump
out operation
Press “K1” button for assigning
the outdoor unit *1)
Push “K4” button 4 times for
checking low pressure
*1) Press 1 time Main Outdoor unit
2 times Sub 1 Outdoor unit
3 times Sub 2 Outdoor unit
4 times Sub 3 Outdoor unit
2kgf/㎠
operating outdoor unit
Press “K2” button 2 times
or “K3” button 1 time
for the end of pump out operation