3. Guideline for each installation process
52
4. Refrigerant pipe construction
4-1. Drawing review
1) Compare the actual site with the drawing. When installing the refrigerant pipes, check
interferences and the requirements for each pipe diameter size/length/quantity ahead of time.
Temper grade and minimum thickness of the refrigerant pipe
Outer diameter Minimum thickness Temper grade
6.35 0.7
C1220T-O
9.52 0.7
12.70 0.8
15.88 1.0
19.05 0.9
C1220T-1/2H
Or
C1220T-H
22.23 0.9
25.40 1.0
28.58 1.1
31.75 1.1
38.10 1.35
44.45 1.6
50.80 2.0
(2) Soft or hard pipes (Annealed, Drawn temper)
Make sure to use C1220T-1/2H(Semi-hard) pipe for more than
19.05mm. In case of using C1220T-O (soft) pipe for 19.05mm, pipe
may be broken, which can result in an injury.